FW-TM Front Film 1 alarms f. DM-TM-x0 - AD-10-1400
TITANUS MICRO·SENS®, is designed for small to medium-sized areas up to 400m² in size. This economical air sampling smoke detector is ideal for use in hotel rooms, offices, and prison cells. The optional ROOM·IDENT feature can localise fires within up to five rooms. It can be configured to use a single primary alarm or a two-stage system (pre-alarm and main alarm).
Thanks to PIPE.GUARD, HPLS light technology and LOGIC·SENS, this air sampling smoke detection system is both highly sensitive and secure against false alarms.
General Features:
- Max. main alarm sensitivity 0.1% obsc./m.
- Coverage up to 400m².
- Up to 50m pipe length and up to 8 aspirating sampling ports.
- Operating temperature: -20°C bis +60°C.
- Optional bar graph smoke level display.
- Dry contacts for connection to any fire panel.
- Optional Ethernet (TCP/IP)/SNMP/data logger.
- Also available as TITANUS MICRO·SENS® cold storage and ROOM·IDENT version.
Technical Data:
Mechanical Data
-
Dimensions mm (W x H x D)
140 x 222 x 70 -
Pipe length (max.)
50m -
Number of sampling points (max.)
8* -
Pipe inlets
1 -
Area of coverage (max.)
400m² -
Number of Alarm Thresholds per detector module
1
Ambient Conditions
-
Temperature range
–20°C to +60°C -
Temperature range, deep freeze variant
–40°C to +60°C -
Rel. humidity (non-condensing)
10 up to 95% -
IP Rating
IP 54
Electrical Data
-
Quiescent current, starting current (1 detector module)
105 mA**, 150 mA** -
Alarm current with bar graph and without bar graph
140 mA**, 110 mA** -
Approvals
EN 54-20, EN 54-17
* via special project planning: 12 sampling points
** at 9 V standard fan voltage