TITANUS®FUSION, is an affordable high-end air sampling smoke detector that combines decades of experience in early fire detection with innovative engineering. The smoke detection system offers a great deal of planning flexibility: it can reliably monitor a wide range of areas of up to 3,200m² in size and can detect even the tiniest quantities of smoke particles early on.

TITANUS®FUSION is a modular ASD and consist of the basic device (1), one or two detector modules (2) and an adhesive front film sheet (3) which can be selected from the below combinations.

General Features:

  • Max. fire alarm sensitivity 0.015% obsc. /m.
  • System coverage up to 2 x 1,600 m².
  • Operating temperature: from -30°C up to 60°C depending on version.
  • Up to 2 x 160m pipe length and depending on detector types up to
  • 1 x 100 or 2 x 72 sampling ports.
  • Free slots for integration of additional modules such as bus modules.
  • Pre-alarm optional via 2nd detector module.
  • Sound pressure level from 23dB(A) for SILENT version

Technical Data

Mechanical Data

  • Dimensions mm (W x H x D)
    140 x 222 x 70
  • Pipe length (max.)
    2 x 160m
  • Number of sampling points (max.)
    1 x 100; 2 x 63
    (SL: 2 x 72*)
  • Pipe inlets
    2
  • Area of coverage (max.)
    2 x 1,600m²
  • Number of Alarm Thresholds per detector module
    1

Ambient Conditions

  • Temperature range
    –30°C to +60°C
  • Temperature range, silent variant
    0°C to +60°C
  • Rel. humidity (non-condensing)
    10 up to 95%
  • IP Rating (Optional)
    IP 20 (IP 52)

Electrical Data

  • Supply voltage
    24 V DC (14 ..30 V DC)
  • Quiescent current, starting current (1 detector module)**
    200 mA, 300 mA
  • Quiescent current, starting current (2 detector modules)**
    220 mA, 320 mA
  • Alarm current with and without reset circuit board (1 detector module)**
    20 mA, 210 mA
  • Alarm current with rand without reset circuit board (2 detector modules)**
    20 mA, 240 mA
  • Approvals
    EN 54-20, EN 54-17

*Fan controller FC-3 necessary, otherwise 63 ports

** at 6.9 V standard fan voltage