Skip to content
Global Fire Systems Specialists, suppliers of Tyco, Simplex, Scami Sistemi & Consilium
Global Fire Systems Specialists, suppliers of Tyco, Simplex, Scami Sistemi & Consilium

Scami Sistemi - Honeywell HS-81 - S81-F4002 Two Channel Analog Input Card

SKU S81-F4002

Two 4-21 mA analog input card, with two thresholds that can be set through the panel keyboard.

It can manage gas detection systems, as well as level and temperature signal systems.

It can control all the 4-20 mA output transducers normally used for EXPLOSIVE and TOXIC GAS, OXYGEN, TEMPERATURE and LEVEL sensors.

Main Characteristics

• Suitable for Redundant Applications 
• Can be hot-swapped 
• Suitable for applications fault-tolerant SIL2 or SIL3 according to the norm IEC61508
• 0-999 display reads engineered values
• Values can be expressed in ppm, LEL%, O2%, mA, °C
• LED bar shows signal trend
• Plastic pocket contains label indicating selected measuring scale
• 4-24 mA input (for fault indication of the sensor)
• Input repetition on 4-20 mA output in terminal block and serial modbus RTU
• Two separately settable alarm thresholds
• Automatic self-testing every 10 seconds
• Communication management by FPGA
• Internal logic management by micro-controller
• Front plug-in on 19'' rack, with locking screws

Compare products

{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}

Select first item to compare

Select second item to compare

Select third item to compare

Compare