DIM800 Detector Input Monitor - 555.800.012
The DIM800 is designed to power and monitor a circuit of low voltage conventional detectors and callpoints. The detection circuit is powered from an external 24V d.c. supply and is reset by the MZX panel. The DIM800 monitors the external 24Vdc and provides a fault signal if it is lost. The input detection circuit can be wired as one or two spur circuits (Class B), one loop configured circuit (Class A) or one 4 wire detection circuit. The module is designed to be compatible with most conventional detection products. Compatibility has been tested to date on the following products: M300 Series, M601 Series, S100 Series, H Series, S231F, S231F+ & CP200.
Technical Information:
-
EMC/RFI:
Equal or exceeds EN50081-1 & EN50130-4 -
Operating Temp:
-25°C to +70°C -
Relative Humidity:
Up to 95% RH non-condensing -
Dimensions:
14H x 148W x 87D mm -
Weight:
100g