Skip to content
Global Fire Systems Specialists, Approved suppliers of Tyco, Simplex, Scami Sistemi & Consilium
Global Fire Systems Specialists, Approved suppliers of Tyco, Simplex, Scami Sistemi & Consilium

LPSY865 Symphoni IP65 Addressable Sounder - 516.800.962

SKU 516.800.962
by Zettler

LPSY865 Symphoni IP65 Addressable Sounder IP65 Red Body for Outdoor Use.

Models Available

The Sounder only models are available with a red or white housing suitable for indoor use and an IP65 rated red housing for outdoor applications. The Audio / Visual models, which incorporate a highly efficient white LED beacon, are also available with a red or white housing for indoor use and an IP65 rated red housing for outdoor applications.

Reflective Sound Monitoring

The LP Symphoni utilising Reflective Sound Monitoring (RSM) employs a transducer to actively monitor the units’ sound output during the weekly sounder test and will report back to the control panel if it fails to detect the sounder operating when it has been commanded to, this ensures that the LP Symphoni range of sounders will in the unlikely event of a fault, display it immediately on the fire controller and is therefore not dependant upon the staff within a building reporting a sounder failure.

Built-in Isolation

As the line isolator is now integral to the device the need for separate line isolation devices is reduced.

Tones

16 Tones are available from the sounder, which include tones compatible with the 802SB sounder base and the LPBB520 (loop powered Besson Banshee). Dutch slow whoop and the DIN 1Hz sweep are included. Two sound levels 103dB & 90dB (±3dB).

EN54 Compliant

The addressable loop powered sounder meets the requirements of EN54 part 3 whilst the loop powered addressable sounder with beacon is also approved to EN54 part 23 as an open category device.

Features:

  • Loop Powered – Reduced installation costs
  • High Output/Low consumption – Lower lifetime costs
  • Indoor and Outdoor models – Same sounder tones in all areas
  • Sounder/LED Beacon Version
  • 16 Tones and 2 Flash rates – Suits individual requirements
  • Reflective Sound Monitoring RSM - Reassurance that ALL sounders are working
  • Integral Line Isolator – Saves cost and installation time
  • Visual alarm approved to EN54-23 open category
  • Audible alarm approved to EN54-3

Technical Information:

  • Operating Temp:
    • Indoor devices:
      -10°C to +55°C
    • Outdoor devices:
      -20°C to +70°C
  • IP rating:
    • Indoor devices:
      IP21C
    • Outdoor devices:
      IP65
  • EMC:
    Product family standard EN50130- 4 in respect of Conducted Disturbances, Radiated Immunity, Electrostatic Discharge, Fast Transients and Slow High Energy EN61000-6-3 for Emissions

Compare products

{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}

Select first item to compare

Select second item to compare

Select third item to compare

Compare